1 GREEN FLASH
Coleman System in Idle / Normal Standby

The status LED flashes green once, repeatedly; the furnace does not start the heating cycle.

Advertisements

Possible Causes

No call for heat from the thermostat, the thermostat not configured for a gas furnace, an open R or W circuit, or low 24 VAC transformer output.

How to Fix / Troubleshooting

Steps to check:

  • Confirm thermostat call: Set the thermostat to HEAT and raise the setpoint. Listen for a click at the thermostat. If none, the thermostat may be faulty.
  • Measure 24 VAC: At the control board, measure between R and C. You should see approximately 24 VAC. If low or zero, check the furnace transformer and primary power.
  • Check R and W continuity: With power off, check resistance between R and W at the furnace with the thermostat calling for heat. A closed circuit should read near 0 ohms. An open reading indicates a break in the thermostat or wiring.

Replace the thermostat or repair wiring as needed. If transformer output is low, replace the transformer with a Coleman-compatible 24 VAC unit.