E12
Certikin
External Control Input Fault
Pump controller displays E12 and ignores external start/stop commands from BMS or timer.
Advertisements
Safety Warning
This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.
If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.
Advertisements
Possible Causes
Open circuit in remote start/stop wiring, incorrect digital input configuration, failed input terminals on controller
How to Fix / Troubleshooting
Safety: Isolate control circuits before testing continuity.
- Check wiring: Trace the remote start/stop or enable signal wiring from the BMS/timer to the Certikin controller. Repair any breaks or loose connections.
- Test inputs: At the controller, bridge the digital input terminals with a short link (as per manual) to simulate a start command. If the pump starts, the external wiring is at fault.
- Verify configuration: In the controller menu, confirm that the correct digital input is assigned to start/stop and that logic (NO/NC) matches the external device.
If the input terminals do not respond even when bridged, the controller input board may need replacement.