Automatic Transfer Failure
Generator will not switch load automatically during mains failure but runs in manual mode.
Advertisements
Safety Warning
This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.
If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.
Advertisements
Possible Causes
ATS control circuit fault, incorrect ATS control wiring from the generator, failed ATS coil or mechanism, controller auto mode disabled or misconfigured.
How to Fix / Troubleshooting
Safety first: Only qualified personnel should work on ATS equipment. Isolate sources as required.
- Verify controller mode: Ensure the FG Wilson controller is in AUTO and that remote start/stop is enabled.
- Simulate mains failure: Under controlled conditions, remove mains sensing and observe if the generator starts and the ATS receives a transfer signal.
- Check ATS control wiring: Confirm that the generator's transfer command contacts are correctly wired to the ATS coil/control terminals.
- Inspect ATS mechanism: Listen for coil operation when transfer is commanded. If silent, test coil voltage and replace the coil or mechanism as needed.
Advertisements
Repair Difficulty
Hard
4/5
Required Part
Automatic Transfer Switch (ATS) Coil