NTI Control / Thermostat Interface Problem

The boiler display shows normal operation, but thermostats do not call for heat or the boiler does not respond to a call.

Advertisements

Possible Causes

Incorrect thermostat wiring, faulty thermostat, broken low-voltage cable, misconfigured control inputs.

How to Fix / Troubleshooting

Safety: Turn off power before changing thermostat wiring.

  • Verify wiring: Compare thermostat wiring to the NTI installation manual. Ensure call for heat terminals are correctly used.
  • Bypass test: Temporarily jumper the call for heat terminals at the boiler. If it starts, the issue is in the thermostat or wiring.
  • Check settings: Confirm the control is configured for external thermostat operation and not locked in manual or test mode.
  • Replace thermostat: If wiring is intact and the boiler responds to a jumper, replace the thermostat.
Advertisements

Repair Difficulty

Easy 2/5

Required Part

Room Thermostat